Product Highlights
Automatic switch over between supplies.
Switches power when mains (utility) supply fails and switches back when mains (utility) supply returns.
Manual restore to S1.
Allows flexible control of source inputs.
Configurable inputs/outputs (10/5).
Provides multiple installation options.
Optional current monitoring.
Provides accurate information on over and under current conditions.
Source 1/source 2 control.
Allows flexible control of source inputs.
Check sync feature.
Ensures the smoothest possible transfer is achieved.
Compatible with DSE160 power supply.
When no DC supply is available the DSE160 power supply connects to an AC power supply and then to the control module.
DSE Configuration Suite PC Software.
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Configurable event log (10).
Provides access to historical alarms and operational status.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
292 mA at 12 V, 167 mA at 24 V
MAXIMUM STANDBY CURRENT
101 mA at 12 V, 66 mA at 24 V
MAINS (UTILITY)
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUT A (MAINS/UTILITY/S1)
Normally closed volt-free output 8 A AC at 250 V AC
OUTPUT B (GENERATOR/S2)
Normally open volt-free output 8 A AC at 250 V AC
OUTPUT C (START AND RUN)
Normally closed volt-free output 8 A DC at 35 V DC (UL Rating 30 V)
OUTPUT D
Changeover volt-free output 8 A AC at 250 V AC
OUTPUT E
Normally open volt-free output 8 A AC at 250 V AC
GENERATOR
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz