Product Highlights
DIN rail & chassis mount.
Power on/link lost LED.
1.2km (0.75 Mile) working range.
Connect maximum of 4 x DSE2133’s to a single host controller.
Rotary ID switch to select address of DSE2133 to talk with host module when multiple DSE2133 modules are in use.
Max of 32 RTD/thermocouple inputs.
Compatible with J-type and K-type thermocouple, PT 100 and 3 wire RTD sensors.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8V to 35V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs
will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
292 mA at 12 V, 167 mA at 24 V
MAXIMUM STANDBY CURRENT
101 mA at 12 V, 66 mA at 24 V
INPUT
8 inputs configurable as RTD/Thermocouple