Product Highlights
Large back-lit icon LCD display.
Displays information to the operator in a clear and concise format.
3-phase generator sensing.
Provides true generator sensing.
3-phase generator and mains (utility) sensing.
Provides true generator and mains (utility) sensing.
600 V ph-ph nominal system compatibility.
Provides global flexibility.
Generator & load power monitoring (kW, kV A, kV Ar, pf).
Provides clear accurate power measurement information.
Generator overload protection (kW).
Provides engine overload protection.
Configurable inputs & outputs.
Provides multiple installation options.
Fuel & crank outputs.
Provides multiple installation options.
Magnetic pick-up speed sensing.
Provides full monitoring flexibility.
Engine speed protection, engine hours counter, engine pre-heat, engine run-time scheduler, engine idle control for start/stop.
Ensures the engine is fully monitored for improved operating performance.
Battery voltage monitoring.
Ensures the battery maintains enough power at all times.
Configurable event log (50).
Provides access to historical alarms and operational status.
DSE Configuration Suite PC Software.
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
85 mA at 12 V, 96 mA at 24 V
MAXIMUM STANDBY CURRENT
51 mA at 12 V, 47 mA at 24 V
MAXIMUM SLEEP CURRENT
35 mA at 12 V, 32 mA at 24 V
MAXIMUM DEEP SLEEP CURRENT
<10 uA at 12 V, <10 uA at 24 V
MAINS (UTILITY)
VOLTAGE RANGE
15 V to 415 V AC (Ph-N)
26 V to 719 V AC (Ph – Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at supply voltage
OUTPUT B (START)
10 A short term, 5 A continuous,
at supply voltage
AUXILIARY OUTPUTs C & D
2 A DC at supply voltage
AUXILIARY OUTPUTs E & F
2 A DC at supply voltage
GENERATOR
VOLTAGE RANGE
15 V to 415 V AC (Ph-N)
26 V to 719 V (Ph – Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)