Support for 0-10 V & 4-20mA oil pressure senders.
Provides flexibility for use with multiple sensors and engine types.
Large back-lit icon LCD display.
Displays information to the operator in a clear and concise format.
Heated display option.
Ensures the display continues to operate in extreme cold weather conditions.
3-phase generator sensing.
Provides true generator sensing.
Breaker control buttons on front fascia.
Instant breaker control when working with a control module.
Generator & load power monitoring (kW, kV A, kV Ar, pf).
Provides clear accurate power measurement information.
Generator overload protection (kW).
Provides engine overload protection.
Generator/load current monitoring & protection.
Provides convenience of monitoring and protection of the generator or monitoring of the load current.
Configurable analogue/digital inputs.
Provides multiple installation options.
Configurable DC, volt-free and staged loading outputs.
Provides full generator load control.
CAN, MPU & alternator speed sensing (selectable depending on engine type).
Makes the module ideal for standard and electronic engine applications.
Tier 4 CAN engine support.
Ensures the control module can be used with the latest in modern electronic engine technology.
Configurable event log (50).
Provides access to historical alarms and operational status.
DSE Configuration Suite PC Software.
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Fuel and start outputs (configurable on CAN).
Provides multiple installation options.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
100 mA at 12 V, 105 mA at 24 V
MAXIMUM STANDBY CURRENT
60 mA at 12 V, 55 mA at 24 V
MAXIMUM SLEEP CURRENT
40 mA at 12 V, 35 mA at 24 V
GENERATOR & MAINS (UTILITY)
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
INPUTS
DIGITAL INPUTS A to F
Negative switching
ANALOGUE INPUTS A to C
Configurable as:
Negative switching digital input
0 Ω to 480 Ω
ANALOGUE INPUT D
Configurable as:
Negative switching digital input
0 V to 10 V
4 mA to 20 mA
0 Ω to 480 Ω
OUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at supply voltage
OUTPUT B (START)
10 A short term, 5 A continuous,
at supply voltage
AUXILIARY OUTPUTs C, D, E & F
2 A DC at supply voltage