Product Highlights
Front panel key switch.
Ensures the generator can only be operated when the key is used.
Configurable for use as a manual or auto start control module.
Helps to reduce module variants held in stock.
Auxiliary shutdown input (manual mode only).
Provides a simple input for a remote stop switch.
LED status indication.
Provides instant generator operating status.
Engine pre-heat.
Warms the engine to a safe temperature at start-up to increase engine life.
Engine monitoring & protection.
Protects engine from long-term damage.
Over speed protection.
Prevents engines running too fast and becoming damaged.
DSE Configuration Suite Lite PC Software (DSE813 required).
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Monitors battery charging status using the WL terminal on the charge alternator.
When the battery has a charging fault the module illuminates an LED on its front panel.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without internal batteries.
MAXIMUN OPERATING CURRENT
26 mA at 12 V, 27 mA at 24 V
MAXIMUM STANDBY CURRENT
20 mA at 12 V, 21 mA at 24 V
CHARGE/FAIL EXITATION RANGE
0 V TO 35 V
OUTPUTS
START
Solid state 1.2 A negative grounding terminal
RUN
Solid state 1.2 A negative grounding terminal
PRE-HEAT
Solid state 1.2 A negative grounding terminal
GENERATOR
VOLTAGE RANGE
15 V – 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz