Product Highlights
Automatic/manual start with configurable start/stop timers.
Offers flexibility to control the module manually, remotely or on pre-set timers and start/stop according to battery condition.
Configurable inputs/outputs (10/8).
Provides multiple installation options.
Mains (Utility) failure detection.
Gives full mains (utility) back up.
AC/DC voltage measurement.
Provides flexibility for use on AC or DC systems.
Battery temperature monitor/charge remaining display/depth of discharge display.
Provides information on battery temperature, charge remaining and depth of discharge.
Backed-up real time clock.
Ensures data is not lost when module is disconnected from its power source.
Configurable event log (250).
Provides access to historical alarms and operational status.
Battery condition automatic start/stop.
Avoids the battery draining completely by starting the generator when the battery needs charging.
USB, RS232, RS485, Ethernet and Modbus RTU/TCP communications.
Provides secure and simple off site monitoring. All ports are continuously active.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
260 mA at 12 V, 130 mA at 24 V
MAXIMUM STANDBY CURRENT
120 mA at 12 V, 65 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage
OUTPUT B (START)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
AUXILIARY OUTPUTS E,F,G,H,I & J
2 A DC at supply voltage
GENERATOR
VOLTAGE RANGE
15 V to 150 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAINS (UTILITY)
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)