Product Highlights
Front panel mounting.
Gives options to reduce wiring at the front of a panel when space is limited.
Remote communications (RS232, RS485 x2, Ethernet).
Provides secure and simple off site monitoring. All ports are continuously active.
Displays the information in the same format as the DSE8610 and DSE8660 control modules.
Provides the exact functionality customers expect from DSE but delivers it in a two-part solution for panels with limited wiring space.
Works with DSE8610, DSE8620, DSE8660, DSE8710, DSE8760, DSE8810 and DSE8660.
Provides high levels of flexibility across multiple load share platforms.
Specification
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
DSE871x max @ 24 V = 70 mA
DSE871x max @ 12 V = 140 mA
OUTPUTS
AUXILLARY OUTPUTS C & D
2 A DC at supply voltage