Product Highlights
Soft start ramping.
Helps to minimise voltage overshoot.
Under frequency roll off protection with optional instantaneous step.
Loss of voltage sensing protection.
Detects disconnection of the voltage sensing connections.
Over excitation protection.
Protects AVR & alternator.
Remote voltage adjustment using -10 V to 10 V signal and 5kΩ potentiometer.
Provides adjustments for voltage set points.
Remote voltage adjustment potentiometer open circuit protection.
Protects against wiring faults.
LED Indication for fault and operating status.
Provides comprehensive and clear indication of operation and parameters.
Chassis mount potted enclosure.
Provides protection against moisture.
Spade terminals.
Quick secure connection.
DIP Switch selection.
Provides voltage, frequency and stability selection.
Specification
POWER SUPPLY
VOLTAGE RANGE
100 V AC to 300 V AC (Ph to N/Ph)
FREQUENCY RANGE
40 Hz to 180 Hz
ALTERNATOR OUTPUT SENSING
VOLTAGE RANGE
15 V AC to 600 V AC (Ph to N/Ph)
FREQUENCY RANGE
40 Hz to 65 Hz
EXCITATION OUTPUT
EXCITATOR FIELD WINDING IMPEDANCE
5 Ω to 50 Ω
CONTINUOUS VOLTAGE RATING
0 V DC to 100 V DC
CONTINUOUS CURRENT RATING
0 A DC to 7 A DC
MAXIMUM CURRENT RATING
15 A DC for 10 seconds
QUADRATURE DROOP CT
MAXIMUM SECONDARY CURRENT
5 A AC
BURDEN
0.25 VA
ACCURACY
1%
REMOTE VOLTAGE ADJUSTMENT
POTENTIOMETER
5 kΩ
VOLTAGE INPUT
-10 V DC to 10 V DC