Features
Voltage regulation < +/-1%
Soft start voltage ramping
Sensing voltage loss protection
120 or 240 Vac sensing, jumper selectable
Under frequency roll off protection
With under frequency LED indicator
Use with Kutai EP200 Paralleling Module for parallel operation
Specifications
Sensing Input
Voltage
120 (95 to 132) or 240 (190 to 264) Vac
1 phase 2 wire jumper selectable
Frequency
50/60 Hz jumper selectable
Output
Voltage
Max. 90 Vdc @ 207 Vac input
Current
Continuous 4A
Intermittent 6A for 10 seconds
Resistance
Min. 15 ohms
Voltage Regulation
< +/-1% (with 4% engine governing)
Build Up Voltage
Residual volts at AVR terminal > 5 Vac @ 25 Hz
Soft Start Ramp Time
2 seconds
External Volts Adjustment
+/-7% with 1 kΩ 1 watt trimmer
Unit Power Dissipation
Max. 10 watts
Thermal Drift
0.05% per °C change in AVR ambient
Under Frequency Protection
Set Point
95% Hz (Factory Knee Point Setting)
Slope
170% down to 30 Hz