The DSE8620MKII represents the latest in complex load sharing & synchronising control technology. Designed to synchronise a single genset with a mains (utility) supply, the DSE8620MKII control module is packed with multiple features and benefits that are unrivalled across the generator control industry.

The controller also has the option to be configured for use as a DSE8610MKII Auto Start Load Sharing & Synchronising Control Module. When converted for use as a DSE8610MKII the unit provides generator to generator load share functionality.

OVERALL SIZE
245 mm x 184 mm x 51 mm (9.6″ x 7.2″ x 2.0″)

PANEL CUTOUT SIZE
220 mm x 160 mm (8.7″ x 6.3″)

MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)

WEIGHT
0.88kg

เปรียบเทียบสินค้า

Product Highlights

Extended PLC function types.
Provides ultimate flexibility for complex grid type generator installations.

Redundant MSC.
Allows two MSC links to be connected between multiple DSE86xx MKII control modules.

Type 1 fully flexible inputs.
Flexible for configuration as voltage, current or resistive.

Two RS485 ports.
Aids communication with electronic engines and building management systems.

Three CAN ports.
Ultimate CAN flexibility. Connect to DSENet devices, communicate with electronic engines and maintain a redundant MSC link.

32-set synchronisation.
Offers optimum flexibility for system expansion.

Configurable inputs/outputs (12/8).
Provides multiple installation options.

Dead bus sensing.
Provides rapid power delivery on multi-set systems.

Remote communications (RS232, RS485, Ethernet).
Provides secure and simple off site monitoring. All ports are continuously active.

Direct governor control.
Eliminates the requirement for external control equipment.

kW & kV Ar load sharing.
Provides controlled power delivery.

Configurable event log (250).
Provides access to historical alarms and operational status.

Load switching, load shedding & dummy load outputs.
Allows load options and dummy load requirements to be independently controlled.

Power monitoring (kW h, kVAr, kv Ah, kV Ar h), reverse power protection, kW overload protection.
Provides clear accurate power measurement information.

Data logging (USB Memory Stick).
Provides current and historical status information.

DSE Configuration Suite PC Software.
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.

Tier 4F Stage V CAN engine support.
Ensures the control module can be used with the latest in modern electronic engine technology.

Sophisticated emission control with DPF regeneration & soot capture.
When soot loading in the filters reaches a set limit the control module can control the regeneration to lower soot levels in the DPF.

Separate ramp up and ramp down rates configurable via PLC.
Enables different values to be configured.

In-built SNMP.
Provides additional flexibility.

Battery charger support across DSENet®.
View connected charger information on the display of the control module.

Configurable CAN transmit and receive.
Provides additional flexibility.

Sophisticated data logging.
Provides detailed site data for detailed analysis.

Support for 0-10 V & 4-20mA sensors.
On-board analogue input supports 3rd party equipment as standard.

Can be configured for use as a DSE8610 MKII.
Provides flexibility to the end user.

Can be used as a rear mounted solution using a DSE rear mount panel bracket.
Gives flexibility to use the product in the front or rear of a panel.


Specification

DC SUPPLY

CONTINUOUS VOLTAGE RATING
5 V to 35 V Continuous

CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries

MAXIMUM OPERATING CURRENT
530 mA at 12 V, 280 mA at 24 V

MAXIMUM STANDBY CURRENT
320 mA at 12 V, 160 mA at 24 V

CHARGE FAIL/EXCITATION RANGE
0 V to 35 V

OUTPUTS

OUTPUT A (FUEL)
15 A DC at supply voltage

OUTPUT B (START)
15 A DC at supply voltage

OUTPUTS C & D
8 A 250 V (Volt free)

AUXILIARY OUTPUTS E,F,G
2 A DC at supply voltage

GENERATOR & BUS

VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE
3.5 Hz to 75 Hz

MAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V

FREQUENCY RANGE
10,000 Hz (max)

BUILT-IN GOVERNOR CONTROL

MINIMUM LOAD IMPEDANCE
500Ω
Fully isolated

GAIN VOLTAGE
0 V to 10 V DC
Fully isolated

OFFSET VOLTAGE
0 V to 10 V DC
Fully isolated

BUILT-IN AVR CONTROL

MINIMUM LOAD IMPEDANCE
1000Ω
Fully isolated

GAIN VOLTAGE
0 V to 10 V DC
Fully isolated

OFFSET VOLTAGE
+/- 10 V DC
Fully isolated