Product Highlights
Configurable DC outputs (4).
Provides the option to tailor the operation to meet system demands.
Configurable analogue/digital inputs (3).
Provides a comprehensive range of multiple monitoring options.
Configurable digital inputs (4).
Provides a comprehensive range of multiple monitoring options.
Engine maintenance alarms (3).
Supports efficient maintenance schedules.
Fuel and start outputs.
Dedicated outputs for simple connection.
Configurable event log (50).
Assists fault finding and operating trends.
Engine pre-heat.
Prevents engines from starting when too cold.
Engine speed protection.
Protects the engine.
Engine hours counter.
Can be used to schedule servicing schedules.
Engine run time scheduler.
Allows engine to be run at pre-configured times.
Battery voltage monitoring.
Detects if the battery voltage drops.
Start on low battery.
Allows engine to be started when connected battery is at low voltage.
LCD alarm indication.
Presents alarm status clearly on the front display.
Power save mode.
Saves energy.
Front panel/PC software configuration.
Flexible configuration for the user.
Specification
DC SUPPLY
CONTINUOUS VOTLAGE RATING
8 V to 35 V continuous
CRANKING DROPUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.
MAXIMUM OPERATING CURRENT
85 mA at 12 V, 96 mA at 24 V
MAXIMUM STANDBY CURRENT
51 mA at 12 V, 47 mA at 24 V
MAXIMUM SLEEP CURRENT
35 mA at 12 V, 32 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
INPUTS
DIGITAL INPUTS A to D
Negative switching
ANALOGUE INPUTS A to C
Configurable as:
Negative switching digital input
Resistive
OUTPUTS
DC OUTPUT A (FUEL) & B (START)
10 A short-term
5 A continuous at supply voltage
VOLT-FREE OUTPUTS C & D
2 A DC at supply voltage
AUXILIARY OUTPUTS C, D, E & F
2 A DC at supply voltage
PULSE PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
5 Hz to 10,000 Hz